Agreements with two major carriers to provide additional diesel fuel
Generators assumes building load within 20 seconds
Generators are tested on weekly basis under load
Tanks are kept at least 80% full at all times
Two utility feeds from independent substations
Diverse paths to the building
Feeds to building are encased in concrete
Fed from two independent substations
Separate transformers fed from both utility sources for redundancy
HVAC chiller systems
Hosting space HVAC system includes (16) AHUs and (16) ACCUs manufactured
by Trane
AHUs are DX type and located in the mechanical mezzanine; the ACCUs
are located on the roof
There is adequate capacity to withstand a HVAC unit failure or an entire
bus failure
Cooling is provided by both overhead and under floor air
HVAC systems have wetted media for humidification, VFDs for each supply
fan, exhaust fans to control building pressure, and economizers to utilize
cool outside air
Separate Dectron outside air handling units provide conditioned air
for the hosting space
UPS Room cooling is provided by Trane RTUs in a N+1 configuration
Node room cooling is provided by Liebert DX CRAC units in a N+1 configuration
Network facilities - Main Node Room
Multiple fiber providers for diversity - provides diversity and redundancy
Each vendor can deliver additional bandwidth capacity with minimal turn-around
time
Can be delivered using existing ‘lit’ fiber
Fiber pathways into the Data Center are truly diverse
Fiber enters building in steel conduit from multiple points in the building